STOP PLATBÁM ZA ENERGIE

ZELENÁ ENERGETICKÉ SAMOSTATNOSTI


Mastervolt XS3200 - 2000W síť

36.744,00Kč

Sunmaster XS3200

GENERAL Specifications

Operating temperature: -20 to 60 °C, full power up to 45 °C ambient air temperature, derating -3%/°C acove 45 °C
Relative humidity: maximum 95% non-condensing; PCB has anti-moisture coating
Protection degree
IP44
Safety class
class I (metal housing with earth connection)
Galvanic isolation
yes (safety transformer)
Dimensions (HxWxD)
545x356x145 mm
Weight
10 kg
Product warranty
5 year
SOLAR INPUT (DC) Recommended PV power range 2200 - 3300 Wp
Nominal input power 2650 W DC
Maximum input power 2780 W DC
Start-up power 7 W
Operating voltage range 100 - 600 V DC
MPP voltage range at nom. power 180 - 480 V DC
Maximum voltage 600 V DC
Number of inputs 2 string connections each are connected in parallel
Rated current 15 A
MPP tracker 1 MPP tracker
MPP efficiency 99,9% (Fraunhofer algorithm)
DC connection 2 sets of MultiContact (4 mm) connectors
GRID OUTPUT (AC)
Voltage 230 V AC single phase (184 - 265 V, country dependent)
Nominal output power at 45 °C 2500 W
Maximum output power 2625 W
Nominal current 13 A
Frequency 45 - 65 Hz, country dependent
Power factor > 0.99 at full power
Harmonic distortion (THD) < 3% at full power
Standby power < 0.5 W
European efficiency 94.3% at 400 V
Maximum efficiency 95.4%
AC connection 2.5 - 4 mm² terminal block
Fuse internal PCB fuse

MONITORING
User interface
integrated LCD - display with backlight, 4 buttons and bright diagnostic LED. All relevant AC and DC values plus diagnostic messages
External communication
2 surge protected RS485 connections. 2 Masterbus connections. Max. 20 XS units can be connected to 1 Data Control Pro datalogger
SAFETY REGULATIONS
General
galvanic seperation between DC and AC side by means of a HF safety transformer
Island protection
redundant voltage and frequency window monitoring. Independent cut-off by means of 2-pole relay and solid state switch according to VDE V 0126-1-1:2006
Temperature protection

thermal switch-off at internal over temperature
Safety devices DC side
isolation resistance monitoring • overvoltage detection • inverse polarity protection • current limitation • transients / surges (varistors) • overload protection
Safety devices AC side
current limitation • DC injection protection • short circuit protection (ceramic fuse) • over-/undervoltage and over-/underfrequency monitoring • active anti-islanding algorithm
DC current injection
VDE0126-1-1 / DK5940 / G83 / KSC8536 compliant
REGULATIONS AND DIRECTIVES
CE conformity
yes
EMC directive
89/336/EEC
Emission
EN 55022, class B
Harmonics
EN 61000-3-2
Dips, variations, flicker
EN 61000-4-11 and -3-3
Immunity
EN 55024; EN 61000-4-2 and -3; EN 61000-4-4, -4-5 and -4-6
LV directive
2006/95/EC
Electrical safety
EN 60950-1 v National grid interface req.
VDE 0126-1-1 / DK5940 / RD1663-2000 / K SC 8536 / G83-1 compliant

Přidat do košíku:

  • Kód: XS3200
  • Přepravní hmotnost: 20kg
  • 2 Balení skladem
  • Výrobce: Mastervolt


Tento produkt byl přidán dne Čtvrtek 08. říjen 2009.

Vaše IP adresa je: 23.22.212.158
Copyright © 2013 Solární elektrárny, větrné elektrárny, vodní turbíny, tepelná čerpadla. Powered by Zen Cart